Add:Hebei Xinhe Jingzhuang Development Zone     Tel:086-0319-4861999

Phone:086-18632093999      E-mail: tlwyxl@126.com

 

Copyright © 2018 Tianlong Weiye Cable Co., Ltd. All rights reserved.   冀ICP备16015320号-1 Powered by 300.cn

PRODUCTS

NH-YJV22 power cable

浏览量
Product description

First, the product standard GB12706, 3---91

 

Second, the scope of use

 

This product is used for power transmission and distribution of (U0/U)0.6/1---26/35kv power line.

 

Third, the use of characteristics

 

1. The maximum rated temperature of the cable conductor is 90 °C, and the short-circuit time (maximum duration does not exceed 5S), the maximum temperature of the cable conductor does not exceed 250 °C.
2. The ambient temperature when laying the cable should not be lower than 0 °C
3. Allow bending radius when laying: single core cable is not less than 15 times the outer diameter of the cable; multi-core cable is not less than 10 times the outer diameter of the cable.

 

Fourth, model, name and conditions of use

 

Model name conditions

YJV YJLV copper (aluminum) core cross-linked PVC insulated and sheathed power cable is laid indoors, in the channel and tube, can also be buried in loose soil, can not withstand external forces, YJV22 YJLV22 copper (aluminum) core cross-linking PVC steel armored sheathed power cable is laid underground, can withstand mechanical external force, but can not withstand large tensile force YJV32 YJLV32 copper (aluminum) core XLPE insulated fine steel wire armored PVC sheathed power cable Suitable for high drop zones, cables can withstand mechanical forces and considerable pull

1. Product use: This product is suitable for power lines with rated voltage (U0/U) of 3.6/6 to 26/35KV for power transmission and distribution.

2, product standard: GB12706-91 rated voltage 35KV and below copper core, aluminum core plastic insulated power cable.

3, product use characteristics:

(1) When the cable is laid at an ambient temperature not lower than 0 °C, it is not necessary to pre-heat. The laying drop of the cable is not limited.
(2) The long-term allowable working temperature of the cable core shall not exceed the following requirements: the outer sheath is a PVC sheathed cable of 90 °C; the outer sheath is a polyethylene sheathed cable of 80 °C.
(3) When the core is short-circuited (maximum 5S), the temperature must not exceed 250 °C
(4) The minimum bending radius for cable laying is as follows: single core cable: 20 (d + D) ± 5%; three core cable: 15 (d + D) ± 5%. Where: D is the actual outer diameter of the cable and d is the actual outer diameter of the conductor.

4, product model, name and scope of use

 

Name Scope of use
Copper core Aluminum core
YJV YJLV XLPE insulated PVC sheathed power cable Fixedly laid in the air, indoors, cable trenches, tunnels or underground
YJY JYLY XLPE insulated PE sheathed power cable Fixedly installed indoors, cable trenches, tunnels or underground
YJV22 YJLV22 XLPE insulated steel tape armored PVC sheathed power cable Fixedly laid in places with external pressure
YJV23 YJLV23 XLPE insulated steel tape armored PE sheathed power cable Fixedly laid in places where external force is often applied
YJV32 YJLV32 XLPE insulated fine steel wire armored PVC sheathed power cable Fixedly laid in places where tensile force is required
YJV33 YJLV33 XLPE insulated fine steel wire armored PE sheathed power cable Fixedly laid in places where tensile force is required
YJV42 JYLV42 XLPE insulated thick steel wire armored PVC sheathed power cable Fixedly laid under water, shaft or where it is required to withstand tension
YJV43 YJLV43 XLPE insulated thick steel wire armored PE sheathed power cable Fixedly laid in places where large tensile force is required

 

Note: One or two single-core cables are not allowed to be laid in iron pipes.

5. Production range

 

Model Number of cores Rated voltage U0/U KV
3.6/6 6/6 6/10 8.7/10 12/20 18/20 21/35 26/35
Conductor core nominal cross section (mm2)
YJLV
YJV
YJLY
YJY
1 25-500 25-500 35-500 50-300
YJLV32
YJV32
YJLY32
JYY32
1 25-500 25-500 35-500 50-300
YJLV42
YJV42
YJLV43
YJV43
1 25-500 25-500 35-500 50-300
YJLV
YJV
YJLY
YJY
3 25-300 25-300 35-300 -
YJLV22
YJV22
YJLV23
YJV23
3 25-300 25-300 35-300 -
YJLV32
YJV32
YJLV33
YJV33
3 25-300 25-300 35-300 -
YJLV42
YJV42
YJLV43
YJV43
3 25-300 25-300 35-150